Power system harmonic resonance-a documented case

TitlePower system harmonic resonance-a documented case
Publication TypeJournal Article
Year of Publication1990
AuthorsLemieux, G.
JournalIndustry Applications, IEEE Transactions on
Volume26
Pagination483 -488
Date Publishedmay.
ISSN0093-9994
Keywords13.8 kV, circuit resonance, electrical faults, failure, harmonics, motor reactance, natural frequencies, power system harmonic resonance, power systems, shunt capacitance, supply reactance, switchgear, voltage levels
Abstract

A case of power system harmonic resonance that resulted in failure of 13.8 kV switchgear and consequent plant losses is documented. Calculations of the power system natural frequencies are given for various power system configurations of supply reactance, motor reactance, and system shunt capacitance. Sources of harmonic current are identified, methods of measuring harmonic current and voltage levels throughout the system are described, and results of the power system harmonic current and voltage survey are reported. Also described is the corrective action taken to prevent a recurrence of harmonic resonance

URLhttp://dx.doi.org/10.1109/28.55959
DOI10.1109/28.55959